Cooling system, cooling system, chiller / industrial water chiller, water chiller for factory
Precise Temperature Control Industrial Cooling System
Thailand is located in a tropical area. The weather is hot all year round. In the use of machinery, electronic equipment and other devices in industrial plants, when the temperature increases, the inside of the machine will overheat, resulting in equipment damage, inefficient operation and if the heat accumulates more and more, it may cause a fire. The heat in the machine is like the heat in a person's body. When our body temperature is higher than normal, we will get sick and will not be able to do things efficiently. Therefore, we take into account the maintenance of the machine and can solve the problem of high temperature machines by: Chiller Be a helper
Thailand is located in the tropical zone. It is hot all year round. In machine operation Electronic device and other industrial equipment when there is an increase in temperature causing the inside of the machine to overheat resulting in malfunctioning equipment not working efficiently and find more and more heat equations there may be a fire. Machine heat Is like the heat of a person's body, when the body temperature increases beyond normal we will get sick and unable to do things at their full potential Therefore, we consider the maintenance of the machine. And can solve problems with high temperature machines with Chiller to help.
Chiller It is a cooling machine, a water chiller, both large and small. Its main function is to produce coolness, reduce the temperature and dissipate heat by using water as the main factor in exchanging and transferring coolness from the chiller. Currently, chillers are used in industrial plants to cool machines, maintain machines to last longer and help maintain the efficiency of the machines.
Chiller is a refrigeration. Water cooler There are both large and small. It is the main function of cold production reduce the temperature and cooling.
Use water as the main medium for exchanging and dissipating heat from the cooling machine.
Chillers are currently used in industrial plants to cool down machines, maintain them for a long time, and help maintain their efficiency.
For example, closed-loop wells, hydraulic injection molding machines, and CNC machines.
For example : Closed system pond, Hydraulic injection molding machine, CNC Engraving Cutting CO2, CNC Laser Engraving UV, CNC Router Milling, CNC Fiber Laser and other.
ขายเครื่องชิลเลอร์ Chiller รุ่น
Used for cooling CNC fiber laser machines. Easy to use, makes the CNC fiber laser machines not hot while working.
FEATURES
Dual digital tube display, set temperature and real-time temperature at a glance.
Full power refrigeration, micro refrigeration, heating control.
With high precision temperature control, fluctuation can be controlled within 0.5℃.
Sensor fault self-diagnosis function water flow alarm function.
The main board adopts high integration chip with strong anti-interference ability.
Machine Dimension
Alarm
Controller page
Top part
inlet and outlet
Displays the water level inside the machine
Drain hole
The device comes with the device
Side of the machine
Back of the machine
Additional function of the drain pipe, can choose to buy inside diameter 19 or 32 mm.
Drainage pipe inside diameter 32 mm
Machine Components
Technical Parameters
Inlet and Outlet
Working between CO2 Laser Tube and Chiller
Additional options: Heat Exchanger
Heat Exchanger Connect to the Chiller and immerse in water to further reduce the water temperature.
The price is only 3,000 baht!!
Installation of Heat Exchanger with chiller
Heat Exchanger Accessories for chillers to further reduce water temperature | SALECNC.net
Chiller Water CoolingVSCooling Tower
Cooling Tower Used in industry Hydraulic Injection Molding Machine Mostly because cooling towers have quite a few disadvantages. The machine is large, it is an open system that is difficult to maintain, dust and sediment are easily able to enter the machine, which negatively affects the operation and shortens the lifespan.
Therefore, the manufacturing industry tends to turn to use Chiller (Chiller Water Cooling) The machine is small, compact, saves working space, is a closed system, prevents dust and sediment well, and has a long service life.
Cooling Tower
Chiller Water Cooling
❌ Open system
❌ Open system operation
✅ Closed system
✅ Closed-system operation
❌ Since the machine is an open system Causing dust and other sediments to enter the machine easily. It will clog, rust and affect the usability of the machine.
❌ Since it works as an open system, dust, debris, etc. are very likely to enter the machine, causing blockage, rust, and definitely affecting the machine's operation.
✅ The machine is a closed system. Prevents dust and other debris from entering the machine. Changing the water is easy.
✅ With a closed system operation, it prevents dust and sediment from entering the machine. Changing water is also convenient.
❌ Cleaning made difficult.
❌ Cleaning the machine is difficult.
✅ Cleaning made easy.
✅ Cleaning the machine is easy.
❌ The machine is large, takes up quite a lot of work space.
❌ The machine is large and requires a lot of working space.
✅ The machine is small, save working space.
✅ The machine is small in size, saving a lot of working space.
❌ Short term
❌ Short lifespan
✅ Long term
✅ Long service life
❌ Cheap… but not worth it !
❌ Cheap but not worth the maintenance, repair and short lifespan, wasting budget in the future.
✅ Expensive… but worth it
✅ More expensive but worth it, easy to maintain and helps reduce costs well.
If interested or have questions, call
061-509-6388 (Chompoo)
098-997-4199 (Fern)
02-312-0227 (office)
E-mail : Sales@salecnc.com
Teaching how to set the temperature of the chiller, making industrial water chiller, model JLFL 1000/1500/2000
Screen and control buttons
Control
3.1 Details
name
details
Current water temperature (PV)
Displays the actual measured water temperature value. In case of malfunction, an error code will be displayed.
Preset water temperature (SV)
Displays the water temperature value set by the user.
Status light
details
Compressor
Flashing light: Compressor is on (Standby) / Steady light: Compressor is working / No light: Compressor is off
Pump
Light on: Pump is working / No light: Pump is off
Heat
Light on: Heater is on / No light: Heater is off (Used for heating water (some models only)
Remote
Light on: Controlled by external signal / No light: No control by external signal
Remote
Light on: Water flows through the valve, valve open / No light: Water does not flow through the valve, valve closed
Run
Light on: Working / No light: Machine is off
Alarm
Light is on: An error has occurred. An error code will be displayed. / Light is off: No error (normal operation).
Push button
details
On/Off
Open, close operation
Set
In case the machine is working normally, you can press the button to enter/exit the set temperature.
▲ ▼
Up and Down
3.2 Boot display
After the controller is powered on, PV and SV will display the software version information and enter the temperature display state after about 7 seconds.
3.3 Temperature display
The PV channel displays the actual measured water temperature, also known as the current temperature.
In the SV channel, the user's set temperature is displayed.
3.4 Error code
When the machine detects a fault at the PV channel, it will display the temperature and error code alternately. In case of detecting multiple faults, you can press the Up or Down button to view.
code
cause
Preliminary fixes
E01
Temperature sensor cannot measure.
–
E02
Water temperature is too high
Leave it open for a while and observe that the water temperature will gradually decrease (the water temperature must be lower than 30 from the factory).
E03
Compressor pressure failure
Remove the water pipe, only the water inlet (Inlet), find something else to hold the water, then turn on the machine.
E04
Electrical phase sequence error
Switch the power to the L, N device.
E05
Water flow is problematic
Check the water pipe for folds, the water flow should be smooth, nothing should block the water path.
E06
Water level too high – too low
Check the water in the tank to see if it is too low or too high (see the water gauge on the back of the machine).
E07
Over load compressor
The compressor is working too hard, turn off the power, turn the compressor blades by hand to see if they rotate smoothly, the electric current is flowing too much.
E08
Low water temperature warning
Water temperature is too low, chances of freezing are high, need to increase water temperature (add hot water).
E09
Room temperature sensor failed
–
E10
Water temperature is too high
Same as E02
E11
Low room temperature
–
E12
Water flow is problematic
Same as E05
[Note]: For errors that need to be reset manually, after eliminating the error, you can press the button. To reset
4. Temperature setting
Press the button (or the gear-shaped symbol)
Press the Up or Down (▲ ▼) buttons to set the temperature.
Press the button Once again, to save
Working characteristics For example, the user sets the temperature at 25 degrees, the compressor will work until the water temperature drops to 23 degrees (according to the factory value, as seen in the current temperature display). After that, the compressor will stop working. When the temperature is more than 27 degrees (according to the factory value), the compressor will start working again.
If you observe, you will see that the temperature has a difference of +/- 2 degrees, which is the factory set value. If the user needs to set the value +/- higher, they can edit the value according to the parameter table.
5. Parameter settings (change factory values)
Condition: User must have knowledge about the machine, otherwise changing the parameters may cause the machine to have problems.
Parameter setting procedure
press+<Down>Leave it for about 3 seconds.
Enter password “XXX” and press button To confirm
Users can set parameters according to the data in the table.
Code
Function
Factory default
Range
Remarks
F01
Room temperature water temperature difference
3.0℃
0.1~9.9℃
Normal temperature water set temperature = [low temperature water set temperature] + [F01 normal temperature water temperature difference] , Not controlled by the upper and lower temperature limits
F01
Automatic working
1
0-1
0: not used / 1: used
F03
Low temperature water set temperature
23.0℃
【F06】~【F05
The function of the parameters is detailed in: 5 Control Logic.
F04
Control temperature difference
1.0℃
0.1~20.0℃
The function of the parameters is detailed in: 5 Control Logic.
F05
Temperature setting upper limit
30.0℃
【F06】~90℃
Low temperature water set the settable temperature range.
F06
Temperature setting lower limit
20.0℃
-38~【F05】℃
Low temperature water set the settable temperature range.
F07
Temperature over temperature upper limit
35℃
0~99℃
Alarm when the temperature of low temperature water or normal temperature water is greater than or equal to this value.
F08
Over temperature lower limit
4℃
-38~99℃
When low temperature water or normal temperature water temperature is less than or equal to this value, it will alarm.
F09
–
F10
Off the compressor temperature difference
3.0℃
0.3~15.0℃
–
F11
Heating temperature difference
2.0℃
0.1~20.0℃
When the electric heating is controlled (that is, the [function selection] is set to 2 or 3), this parameter is valid. / The function of the parameters is detailed in: 5 Control Logic.
F12
Low temperature water temperature compensation
0
-9.9~9.9℃
–
F13
Room temperature water temperature compensation
0
-9.9~9.9℃
Add
F14
Compressor anti-frequent start time
2 minutes
1-5 minutes
–
F15
Compressor start delay
30 seconds
0-255 seconds
Press the start button for at least the set time before allowing the compressor to start
F16
High/low temperature alarm delay
10 seconds
0-255 seconds
After the set time is delayed after the power is turned on, the detection of low temperature water and normal temperature water temperature is too high/low faults.
F17
Flow alarm delay
3 seconds
0-255 seconds
After pressing the power button, it will alarm after detecting the flow switch input for this time
F18
Level alarm delay
5 seconds
0-255 seconds
After power-on, it will alarm after detecting the input of the level switch for this time
F19
Pressure detection delay
10 seconds
0-255 seconds
After turning on the compressor and delaying the set time, start to detect pressure failure.
F20
DI4 input selection
0
0-1
0: Normal temperature flow / 1: Phase sequence switch
F21
Pressure Switch
0
0-2
0: Normally open / 1: Normally closed / 2: Disabled
(When set to normally open, the switch is closed and alarms)
F22
Room temperature flow/phase sequence
0
0-2
0: Normally open / 1: Normally closed / 2: Disabled
(When set to normally open, the switch is closed and alarms)
F23
Low temperature flow switch
0
0-2
When set to normally closed, the switch is disconnected and alarms
/ When set to disable, the state of the corresponding switch is not detected.
F24
Level Switch
0
0-2
When set to normally closed, the switch is disconnected and alarms
/ When set to disable, the state of the corresponding switch is not detected.
F25
Compressor overload switch
0
0-2
When set to normally closed, the switch is disconnected and alarms
/ When set to disable, the state of the corresponding switch is not detected.
F26
Alarm relay function
1
0-1
0: Alarm signal, control the relay output according to whether the unit has a fault
(**Relay NC point: disconnect when the unit fails, and close when the unit is in standby or normal operation; )
(**Relay NO point: pulls in when the unit fails, and disconnects when the unit is in standby or normal operation. )
/ 1: Normal operation signal, according to whether the unit is operating normally to control the relay output
(**Relay NC point: disconnect when the unit is operating correctly, and close when the unit is in standby or failure; )
(**Relay NO point: when the unit is operating correctly, it is closed, and when the unit is in standby or faulty, it is disconnected. )
F27
Bypass Valve Use Selection
1
0-1
0: disable / 1: enable
F28
Bypass valve temperature difference
0.5℃
0.1~9.9℃
–
Control
After the machine starts working, the system will check the water level for 2 seconds. If the water level is too low, the pump will not work.
The compressor solenoid valve and heat controller will start working when the set time [F15 Compressor start delay] is reached.